Hotels run a load that never stops, on roofs that guests can see, in two of the harshest siting environments in the country. Where the panels can go, what the salt air does, and why solar is not back-up power.
A resort general manager can usually tell you two numbers without looking them up: the electricity bill in peak season and what the generator burned last month. Neither number is improved by a solar plant that was designed for a factory roof and dropped onto a hotel, because a hotel is a different load, a different roof and, on the coast, a different environment altogether.
Hotels run around the clock, but not evenly. Guest room air conditioning peaks in the afternoon and again overnight. Corridor and facade lighting, the restaurant and the banquet hall are evening loads. Laundry, kitchen preparation, housekeeping, pool filtration, water pumping and the office block are firmly daytime, and those are the loads a rooftop array will actually displace.
So the useful sizing question is not what the hotel consumes in a day. It is what the hotel consumes between roughly nine in the morning and four in the afternoon, on a low season weekday, when occupancy is at its worst. Size against that floor and the plant is consumed on site all year. Size against a full house in peak season and the plant spends the monsoon exporting units that are settled rather than avoided.
Two levers move that floor in the right direction, and both are free. Laundry can be scheduled into the middle of the day rather than run late at night for the night shift's convenience. Pool filtration and water pumping can be timed to the generation window instead of a timer somebody set at commissioning years ago. On a large property those two changes shift a surprising amount of load into daylight.
A hotel roof is the most contested piece of real estate on the property. Before any array is drawn, walk every roof with the chief engineer and mark what is already there and what is promised to somebody else.
Cox's Bazar, Kuakata, Saint Martin's and the rest of the coastal belt combine salt laden air, high humidity, driven rain and cyclone season wind. A specification written for a Dhaka rooftop will corrode there, and the failures are slow, ugly and expensive to reverse.
This is the conversation to have early, because the expectation is almost always wrong. A grid tied inverter is required to disconnect when the grid fails. It is an anti islanding protection function, it is not optional, and it means that during a load shedding event the array stops even at noon under a clear sky. A hotel that installs solar and still loses the lifts in a power cut has not been badly served. It has been correctly served and badly briefed.
There is a second interaction that catches properties which run a generator regularly. When the hotel is on the diesel set, an array feeding the same board can push the generator into reverse power, which its protection will not tolerate and which can damage the machine. The answer is a controller that either blocks the inverters or limits them to the measured on site load while the generator is running, and it has to be commissioned and tested with the generator, not assumed.
If the property genuinely needs solar backed reserve, it belongs on a defined list of circuits rather than the whole hotel: fire alarm and pumps, emergency and corridor lighting, one lift, the front desk and the servers, the cold rooms. That list is small, it is affordable, and it is the list guests and the fire inspector actually notice.
Resorts in the Sylhet hills and the tea belt have the opposite set of problems. Salt is not the issue. The issues are a long low tension spur from a distant transformer, voltage that swings enough to trip inverters on their own protection settings, tree lines that shade the array for part of the day and grow taller every year, rainfall that overwhelms a badly detailed roof, and site access that decides how big a delivery can reach the property at all.
Two things are worth doing at survey. Log the supply voltage for a full week before selecting inverters, so the grid protection window is set against measured conditions rather than a default. And survey the tree line for what it will be in ten years, not for the shadow on the day of the visit, because the resort will not cut the trees. They are the reason guests come.
Hill sites also make the earthing and lightning protection more than a formality. Exposed ridge positions, tall structures and a hospitality building full of guests is not a combination to leave to a token earth rod. Specify the earthing design, measure the resistance at commissioning and record it.