Skip to main content

Fume hoods and local exhaust ventilation: what protects the operator and what does not

Face velocity, containment testing, ducted against filtered recirculating hoods, and the failures a hood cannot save you from. What to write into a tender so the hood you receive is the hood you specified.

A fume hood that has never been tested is a cupboard with a fan on it. That is not a rhetorical flourish: containment is a property of the whole installation, not of the box, and it is entirely possible for a well-made hood from a good manufacturer to fail to contain because the room has no make-up air, or because a ceiling diffuser blows across its face. Every laboratory we survey has hoods. Rather fewer have hoods with a test report, and fewer still have a test report from after installation rather than from the factory.

Face velocity is a proxy, not the goal

The goal is containment: contaminant generated inside the hood stays inside it and does not reach the operator's breathing zone. Face velocity became the specification because it is cheap to measure and containment is not. It remains a useful indicator, provided you remember what it does not tell you.

Too little face velocity lets contaminant escape at the sash opening. Too much is also a defect, because a fast inward stream separates around the operator's body and forms a vortex at the sash that pulls contaminant back out. Above a certain velocity, adding more makes containment worse while making the energy bill and the noise worse as well. Design practice for a conventional hood sits in a fairly narrow band, and your supplier should state the design face velocity and the design sash height together, because one is meaningless without the other.

When you measure, measure on a grid across the sash opening at the design height with a calibrated thermal anemometer, and record every reading rather than just the average. A hood with an acceptable average and a wide spread between the highest and lowest readings is a hood with a bad baffle setting or an obstruction, and the average is hiding it. The spread is the more informative number.

Containment testing: the test that actually means something

Ducted or filtered recirculating

Ductless hoods are attractive in Dhaka for real reasons: rented floors where you have no rights to a riser or a roof, buildings with no spare shaft, and refurbishments where a duct route simply does not exist. They are a legitimate answer to a narrow question, and a poor answer to a broad one.

ConsiderationDucted hoodFiltered recirculating hood
Chemistry it suitsAnything within the liner's chemical resistance, including changing and unknown workA known, limited, low-volume list matched to a specific filter medium
Where the contaminant goesOut of the building, treated by a scrubber if the discharge requires itOnto a filter, then back into the room once the filter is exhausted
Building workRiser, roof plant, discharge stack, fan, make-up air, structural coordinationA power socket
Running costFan energy plus conditioning the make-up air, which is the bigger figure in this climateFilter replacement, and filters have a shelf life as well as a service life
The failure modeVisible: fan stops, alarm sounds, work stopsInvisible: filter saturates and the hood discharges into the room
Who has to own itBuilding maintenance, on a planned scheduleA named person tracking usage, breakthrough tests and filter dates

Filtered hoods are defensible for a teaching bench doing one known preparation, or a weighing enclosure for powders. They are the wrong choice for a research laboratory whose chemistry changes with each new student, and they are unsuitable for perchloric acid, for high-boiling acid digestions, for radionuclides, and for low molecular weight gases that carbon adsorbs poorly. If you buy one, buy the breakthrough test with it and put the filter change into a maintenance schedule with an owner, or it will be running on an exhausted filter within two years and nobody will know.

What a fume hood cannot protect you from

Commissioning, and the annual test after that

  1. Balance the room first. Establish the supply air and the total extract, and confirm the laboratory sits slightly negative to the corridor. Slightly. If the door needs a shove, the balance is wrong and the hoods are competing with the door seals for air.
  2. Check the discharge before you accept the installation. The stack should discharge upwards at a velocity high enough to carry the plume clear of the roof, and it must be away from fresh air intakes, opening windows and neighbouring roofs. In Dhaka the roof is shared with condensers, water tanks and often a caretaker's quarters, so this needs to be drawn and agreed rather than assumed.
  3. Set and record the baffles. Then mark the setting, because somebody will move it.
  4. Measure face velocity on a grid at the design sash height and record every reading, then run a smoke test and a tracer gas containment test to EN 14175 part 4 with the hood in its as-used state.
  5. Prove the airflow monitor by shutting the fan down and confirming the alarm is audible and visible at the hood, and that a low-flow condition is reported to whoever is responsible for the building.
  6. Label each hood with its design sash height, the date of the last test and the date of the next. A sticker on the sash frame does more for daily safety than a folder in an office.
  7. Retest annually and after any change to the fan, ductwork, room ventilation or adjacent hoods. Adding one hood to a shared manifold changes the balance of every hood on it, which is why the annual test should cover the system rather than each hood in isolation.

Writing the tender so you get the hood you specified

In a competitive e-GP evaluation, anything not named in the bill of quantities is a cost the lowest bidder has already removed. These lines are worth the space they take:

Back to all Insights